| MODEL | 
                  103-FC | 
                  303-FC | 
                  373-FC | 
                  503-FC | 
                  603-FC | 
                  653-FC | 
                  803-FC | 
                  104-FC | 
                 
                
                  | Capacity | 
                  1kVA | 
                  3kVA | 
                  3.75kVA | 
                  5kVA | 
                  6kVA | 
                  6.5kVA | 
                  8kVA | 
                  10kVA | 
                 
                
                  | INPUT | 
                   
                
                  | Voltage | 
                  1P, 100~120V or 200~240Vac | 
                  1P, 220Vac -15%, +25% | 
                 
                
                  | Frequency | 
                  50Hz    or 60Hz ± 5% | 
                   
                  OUTPUT | 
                
                  | Voltage | 
                  1P, 220Vac ± 5% (Adjustable) | 
                 
                
                  | Frequency | 
                  50Hz or 60Hz, 400Hz (Option) ± 0.5% | 
                 
                
                  | Voltage Regulation | 
                  ± 1% | 
                 
                
                  | Frequency Stability | 
                  ± 0.5% (Free running) | 
                 
                
                  | Transient Response | 
                  ± 3% (100% Load variation) | 
                 
                
                  | Waveform | 
                  Sine wave | 
                 
                
                  | Distortion | 
                  < 3% at 0~100%(Linear load) | 
                   
                
                  | Overload Capacity | 
                  105%: 30 sec, 150%: constant power | 
                  120~150%: 30 sec, >150%: constant power | 
                 
                
                  | Power Factor | 
                  0.7-1, lag | 
                 
                
                  | Crest Ratio | 
                  3:1 | 
                 
                  EFFICIENCY | 
                
                  | AC to AC | 
                  >85% | 
                 
                  PROTECTION | 
                
                  | Overload | 
                  105%: 30sec | 
                  120%: 30 sec | 
                 
                
                  | Short Circuit | 
                  Current limited and cut-off and fuse and    breaker | 
                 
                
                  | EMI/EMC | 
                  EN50091-2, CE approved | 
                 
                  AUDIBLE ALARM | 
                
                  | Mains Failure | 
                  Sounding every four seconds after mains fail,    90 seconds mute | 
                 
                
                  | Optional Battery Low | 
                  Sounding    once every second as optional battery low level approaches | 
                  Sounding once every second as battery    approaches | 
                 
                
                  | Overload & UPS Fault | 
                  Continuously | 
                 
                   INDICATOR | 
                
                  | LCD | 
                  I/P&O/P    voltage/ frequency | 
                  I/P&O/P    voltage/frequency, loading %, history record | 
                 
                
                  | LED | 
                  50Hz,    60Hz, overload, fault | 
                  Utility LED (Green), inverter LED    (Green), fault LED (Red), overload (Yellow) | 
                 
                  INTERFACE | 
                
                  | Contact Closure | 
                  Support MEGATEC RUPS UPS monitoring software | 
                 
                
                  | RS-232 | 
                  Support MEGATEC RUPSII / UPSilon 2000    monitoring software | 
                 
                  ENVIRONMENT | 
                
                  | Operation Temperature | 
                  0-40 ℃(32-104 ℉) | 
                 
                
                  | Relative Humidity | 
                  0-90% (non-condensing) | 
                 
                
                  | Audible Noise(At 1M) | 
                  <  45dBA | 
                 
                    PHYSICAL | 
                
                  | Net Weight(kg, without battery) | 
                  20 | 
                  30(400Hz);65(50 or 60Hz) | 
                  60 | 
                  66 | 
                  69 | 
                  94 | 
                  115 | 
                  116 | 
                 
                
                  | Dimension (WxHxD)mm | 
                  180 x 308 x 381 | 
                  180 x 360 x 500 (400Hz) , 
 180 x 500 x 540(50 or 60Hz) | 
                  230 x 685 x 578 | 
                  480 x 845 x 340 | 
                   
                
                  | ✽ All specifications mentioned above are subject to change without prior notice | 
                 
               
            
	          
               
			
            
              
                
                
                  | MODEL | 
                  3104-FC | 
                  3124-FC | 
                  3154-FC | 
                 
                
                  | Capacity | 
                  10 kVA | 
                  12 kVA | 
                  15 kVA | 
                 
                   INPUT | 
                
                  | Voltage | 
                  3P3W, 220V or 3P4W, 220/380V,-15% +25% | 
                 
                
                  | Frequency | 
                  50Hz or 60Hz ± 5% | 
                 
                OUTPUT | 
                
                  | Voltage | 
                  1P, 220Vac ± 5% (Adjustable) | 
                 
                
                  | Frequency | 
                  50Hz or 60Hz, 400Hz (Option) ± 0.5% | 
                 
                
                  | Voltage Regulation | 
                  ± 1% | 
                 
                
                  | Frequency Stability | 
                  ± 0.5% (Free running) | 
                 
                
                  | Transient Response | 
                  ± 3% (100% Load variation) | 
                 
                
                  | Waveform | 
                  Sine wave | 
                 
                
                  | Distortion | 
                  < 3% at 0~100%(Linear load) | 
                 
                
                  | Overload Capacity | 
                  120%: 30 sec, >150% constant power | 
                 
                
                  | Power Factor | 
                  0.7-1, lag | 
                 
                
                  | Crest Ratio | 
                  3:1 | 
                 
                EFFICIENCY | 
                
                  | AC to AC | 
                  >85% | 
                 
                PROTECTION | 
                
                  | Overload | 
                  125%: 30 sec | 
                 
                
                  | Short Circuit | 
                  Current limited and cut-off and fuse and    breaker | 
                 
                
                  | EMI/EMC | 
                  EN50091-2, CE approved | 
                 
                AUDIBLE ALARM | 
                
                  | Mains Failure | 
                  Sounding every four seconds after mains fail,    90 seconds mute | 
                 
                
                  | Final Discharge | 
                  Sounding once every second as battery    approaches | 
                 
                
                  | Overload | 
                  Continuously | 
                 
                  INDICATOR | 
                
                  | LCD | 
                  I/P&O/P voltage / frequency,    loading %, history record | 
                 
                
                  | LED | 
                  Utility LED (Green), inverter LED (Green), fault LED (Red), overload    (Yellow) | 
                 
                INTERFACE | 
                
                  | Contact Closure | 
                  Support MEGATEC RUPS UPS monitoring software | 
                 
                
                  | RS-232 | 
                  Support MEGATEC RUPSII / UPSilon 2000    monitoring software | 
                 
                   ENVIRONMENT | 
                
                  | Operation    Temperature | 
                  0-40 ℃(32-104 ℉) | 
                 
                
                  | Relative Humidity | 
                  0-90% (non-condensing) | 
                 
                
                  | Audible Noise(At 1M) | 
                  < 45dBA | 
                 
                  PHYSICAL | 
                
                  | Net Weight(kg, without battery) | 
                  116 | 
                  120 | 
                  200 | 
                 
                
                  | Dimension (WxHxD)mm | 
                  480    x 845 x 340 | 
                  480    x 885 x 380 | 
                 
                
                  | ✽ All specifications mentioned above are subject to change without prior notice | 
                 
               
            
             
            
            
      
	  
     |