MODEL |
ALP-FC-10K |
ALP-FC-20K |
ALP-FC-30K |
ALP-FC-40K |
ALP-FC-50K |
ALP-FC-60K |
Phase |
3-Phase Input / 3-Phase Output |
kVA |
10 |
20 |
30 |
40 |
50 |
60 |
INPUT (RECTIFIER) |
Input Voltage |
380V/400V/415V, Special specification can be customized |
Input Range |
±20% ( > ± 20% is available upon
request) |
Input Frequency |
50 / 60 Hz ± 5% |
Power Walk In |
20 seconds |
Efficiency |
> 98% |
Voltage Regulation |
1% |
INVERTER |
Output Voltage |
380V/400V/415V, ±1 %, Special specification can be customized |
Wave Form |
Sine wave |
Output Power Factor |
0.8 |
Output Frequency
(Free Running) |
50 / 60 / 400Hz ± 0.1 Hz |
Phase Shift Under 100%
Unbalance Load |
< 0.5° |
THD (Linear Load) |
< 3 % |
Overload |
<110% |
Continuous |
110~124% |
15 minutes |
125~149% |
5 minutes |
≧150% |
30 seconds |
Efficiency (100% Load)
for 380/400/415V, 3P4W |
92% |
93% |
OVERALL CHARACTERISTICS |
Overall Efficiency(100% Load)
for 380/400/415V, 3P4W |
90% |
91% |
Dimensions(H*W*D)mm |
1600 x 550 x 800 |
Weight (Kg, without battery)
for 380/400/415V, 3P4W |
280 |
300 |
400 |
480 |
550 |
680 |
Audible Noise(At 1M) |
< 65 dBA |
Temperature |
0 – 40℃ ( 32 – 104℉ ) |
Humidity |
0% - 90% (non-condensing) |
Altitude |
< 1500M above sea level |
EN50091-1,-2 |
Yes |
Short Circuit Protection |
Yes |
Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
Galvanic Isolation |
Input&Output true galvanic isolation |
LED,LCD,Buzzer |
Yes |
Remote Control /
Communication Interface |
Dry contact, UPSCOM(RS232), Remote control panel(RS485), Modbus(RS485), Netagent(SNMP card) |
✽ The maximum capacity 1000KVA is available for the model
✽Different specifications required are available ✽All specifications mentioned above are subject to change without prior notice |
MODEL |
ALP-FC-80K |
ALP-FC-100K |
ALP-FC-120K |
ALP-FC-160K |
Phase |
3-Phase Input / 3-Phase
Output |
kVA |
80 |
100 |
120 |
160 |
INPUT (RECTIFIER) |
Input Voltage |
380V/400V/415V, Special specification can be customized |
Input Range |
± 20% ( > ± 20% is available upon
request) |
Input Frequency |
50 / 60 Hz ± 5% |
Power Walk In |
20 seconds |
Efficiency |
98% |
Voltage Regulation |
1% |
INVERTER |
Output Voltage |
380V/400V/415V, ±1 %, Special specification can be customized |
Wave Form |
Sine wave |
Output Power Factor |
0.8 |
Output Frequency
(Free Running) |
50/60/400Hz ± 0.1 Hz |
Phase Shift Under 100%
Unbalance Load |
< 0.5° |
THD (Linear Load) |
< 3 % |
Overload |
<110% |
Continuous |
110~124% |
15 minutes |
125~149% |
5 minutes |
≧150% |
30 seconds |
Efficiency (100% Load)
for 380/400/415V, 3P4W |
94% |
94.5% |
OVERALL CHARACTERISTICS |
Overall Efficiency(100% Load)
for 380/400/415V, 3P4W |
92% |
92.5% |
Dimensions(H*W*D)mm |
1600 x 1100 x 800 |
Weight (Kg, without battery)
for 380/400/415V, 3P4W |
820 |
950 |
1180 |
1450 |
Audible Noise(At 1M) |
< 67 dBA |
Temperature |
0 – 40℃ ( 32 – 104℉ ) |
Humidity |
0% - 90% (non-condensing) |
Altitude |
< 1500M above sea level |
EN50091-1,-2 |
Yes |
Short Circuit Protection |
Yes |
Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
Galvanic Isolation |
Input&Output true galvanic isolation |
LED,LCD,Buzzer |
Yes |
Remote Control /
Communication Interface |
Dry contact, UPSCOM(RS232), Remote control panel(RS485), Modbus(RS485), Netagent(SNMP card) |
✽ The maximum capacity 1000KVA is available for the model
✽Different specifications required are available
✽All specifications mentioned above are subject to change without prior notice |
MODEL |
ALP-FC-240K |
ALP-FC-320K |
Phase |
3-Phase Input / 3-Phase
Output |
kVA |
240 |
320 |
INPUT (RECTIFIER) |
Input Voltage |
380V/400V/415V, Special specification can be customized |
Input Range |
± 20% ( > ± 20% is available upon
request) |
Input Frequency |
50/60 Hz ± 5% |
Power Walk In |
20 seconds |
Efficiency |
98% |
Voltage Regulation |
1% |
INVERTER |
Output Voltage |
380V/400V/415V, ±1 %, Special specification can be customized |
Wave Form |
Sine wave |
Output Power Factor |
0.8 |
Output Frequency
(Free Running) |
50/60/400Hz ± 0.1 Hz |
Phase Shift Under 100%
Unbalance Load |
< 0.5° |
THD (Linear Load) |
< 3 % |
Overload |
<110% |
Continuous |
110~124% |
15 minutes |
125~149% |
5 minutes |
≧150% |
30 seconds |
Efficiency (100% Load)
for 380/400/415V, 3P4W |
95% |
OVERALL CHARACTERISTICS |
Overall Efficiency(100% Load)
for 380/400/415V, 3P4W |
93% |
Dimensions(H*W*D)mm |
1600 x 2200 x 800
|
Weight (Kg, without battery)
for 380/400/415V, 3P4W |
1950 |
2450 |
Audible Noise(At 1M) |
< 67 dBA |
Temperature |
0 – 40℃ ( 32 – 104℉ ) |
Humidity |
0% - 90% (non-condensing) |
Altitude |
< 1500M above sea level |
EN50091-1,-2 |
Yes |
Short Circuit Protection |
Yes |
Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
Galvanic Isolation |
Input&Output true galvanic isolation |
LED,LCD,Buzzer |
Yes |
Remote Control /
Communication Interface |
Dry contact, UPSCOM(RS232), Remote control panel(RS485), Modbus(RS485), Netagent(SNMP card) |
✽ The maximum capacity 1000KVA is available for the model
✽Different specifications required are available
✽All specifications mentioned above are subject to change without prior notice |
|