産品 > 不斷電系統 > APA 系列 (True Sine Wave) 650VA-10kVA



UPS
 

特性與優點

純淨正弦波適於線性與非線性負載。
完整系列產品650VA到10kVA
多樣性產品,直立式、機架式1U/2U/3U與可轉換直立/機架式。
標準產品與長時間放電的產品可供使用。
選配的通訊介面卡可選擇( RS232、SNMP card、乾接點、AS-400卡與USB卡。
對過載、過熱、浪湧、突波、短路與過充與防呆的接線安裝…等,有完整的保護。
人性化容易更換電池的設計。
內建具有輸入功率因數校正強而有力的充電器。
機架式選配的緊急斷電(EPO)裝置提供客戶選用。
智能風扇轉速控制
直流啟動
MODEL APA-650 LED APA-103T APA-153T APA-203T
Capacity VA / Watt 650VA/406W 1kVA/625W 1.5kVA/938W 2kVA/1250W
Mode Type Tower
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%  
Buck Return 127Vac ± 2% ; 254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return  145Vac ± 2% ;  290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 12Vdc 24Vdc 36Vdc 36Vdc
Type 9AH 7AH 7AH 9AH
Quantity 1pce 2pcs 3pcs 3pcs
Backup Time > 2min > 3 min
Recharging Current 0.1C 0.1C ~ 0.3C
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage &level, Temperature, Model
LED Normal(Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery  Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard USB  RS232
Multi-Interfaces Card(Option) N/A Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 115*322*130 145*215*365 145*215*431
Net Weight (Kg) w/o battery 3.2 8.6 10.4 12.2
NEMA Outlets
(110/115/120Vac)
3 4 6
IEC  Outlets
(220/230/240Vac)
4 3 6
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
 ✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103U APA-153U
Capacity VA/Watt 1kVA/625W 1.5kVA/938W
Mode Type Rack
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac 
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode  > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc
Type 7AH
Quantity 4pcs
Backup Time > 3 min
Recharging Current 0.1C ~ 0.3C
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model
LED Normal (Green), Warning (Amber), Fault (Red) 
AUDIBLE ALARM
Battery  Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*44*515
Net Weight (Kg) w/o battery 12 14.1
NEMA Outlets
(110/115/120Vac)
4
IEC Outlets
(220/230/240Vac)
5
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah
✽ Dimension:W*H*D=440*132*465mm. 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TR APA-153TR APA-203TR APA-303TR APA-503TR APA-753TR APA-104TR
Capacity VA/ Watt 1kVA/
625W
1.5kVA/
938W
2kVA/
1250W 
3kVA/
1875W
5kVA/
3125W 
7.5kVA/
4688W 
10kVA/
6250W 
Mode Type   Tower & Rack convertible
INPUT
 Nominal Voltage  110/115/120 Vac or 220/230/240Vac   220/230/240Vac 
 Voltage Range Acceptable Voltage Range 85Vac ~ 150Vac or 170Vac ~ 300Vac 170Vac ~ 300Vac
 Frequency  45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%  195.5Vac ± 2% 
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2%  205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2% 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%  254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2% 170Vac ± 2%
Low Voltage Return  90Vac ± 2% ; 180Vac ± 2% 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2% 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;  290Vac ± 2% 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode  50Hz or 60Hz ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown 
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
Battery
Voltage 24Vdc 36Vdc 36Vdc 36Vdc 48Vdc 48Vdc
Type 7AH 7AH 9AH 7AH 9AH 7AH 9AH
Quantity 2pcs 3pcs 3pcs 6pcs 8pcs 16pcs 16pcs
Backup Time > 3 min
Recharging Current 0.1C ~ 0.3C
CONTROL PANEL 
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model  
LED Normal(Green), Warning (Amber), Fault (Red) 
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds 
Low Battery Beeping every second 
UPS Fault Beeping continuously 
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard  RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*88*465 440*132*465 440*132*620 440*132*465
Net Weight (Kg) w/o battery  15.6 17.1 17.5 22.8 29.4  31.4 36.4
NEMA Outlets
(110/115/120Vac) 
 4 8 8+1*
terminal block
4+1*terminal block  
IEC Outlets
(220/230/240Vac)
6 10 10+1*
terminal block
5+1*terminal block
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TRL APA-153TRL APA-203TRL APA-303TRL APA-503TRL APA-753TRL
Capacity VA/Watt 1kVA/625W 1.5kVA/938W 2kVA/1250W 3kVA/1875W 5kVA/3125W 7.5kVA/4688W
Mode Type Tower & Rack convertible
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac  220/230/240Vac
Voltage Range Acceptable Voltage Range 85Vac ~ 150Vac or 170Vac ~ 300Vac 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2% 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 205.5Vac ± 2%
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2% 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%  254.5Vac ± 2%
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%  170Vac ± 2%
Low Voltage Return  90Vac ± 2% ; 180Vac ± 2% 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2% 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;290Vac ± 2% 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage Regulation Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency Regulation Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload Protection Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit Protection Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc  36Vdc 36Vdc 48Vdc
Type N/A
Quantity N/A
Backup Time Based on Load % & Batteries
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model
LED Normal (Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*88*465 440*132*465
Net Weight (Kg) 14 16.4 21 25.5 31.4 36.4
NEMA Outlets
(110/115/120Vac)
6 10 8 4+1*terminal block 4+1*terminal block
IEC Outlets
(220/230/240Vac)
6 10 10 5+1*terminal block 5+1*terminal block
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TL APA-153TL
Capacity VA / Watt 1kVA/625W 1.5kVA/938W
Mode Type  Tower
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ±2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2%
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return 145Vac ± 2% ; 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode  Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency Line Mode  > 98%
Battery Mode > 80%
Overload
Protection
Line Mode  > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker 
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc 36Vdc
Type N/A
Quantity N/A
Backup Time > 3 min
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model 
LED Normal (Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 145*215*365 145*215*431
Net Weight (Kg) 11.6 12.6
NEMA Outlets
(110/115/120Vac)
3 6
IEC Outlets
(220/230/240Vac)
3 6
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽All specifications mentioned above are subject to change without prior notice