MODEL |
APA-650 LED |
APA-103T |
APA-153T |
APA-203T |
Capacity |
VA / Watt |
650VA/406W |
1kVA/625W |
1.5kVA/938W |
2kVA/1250W |
Mode Type |
Tower |
INPUT |
Nominal Voltage |
110/115/120 Vac or 220/230/240Vac |
Voltage Range |
Acceptable
Voltage Range |
85Vac ~ 150Vac or 170Vac ~ 300Vac |
Frequency |
45Hz ~ 70Hz Auto-sensing |
Boost Transfer |
97.8Vac ± 2% ; 195.5Vac ± 2% |
Boost Return |
102.8Vac ± 2% ; 205.5Vac ± 2% |
Buck Transfer |
132Vac ± 2% ; 264.5Vac ± 2% |
Buck Return |
127Vac ± 2% ; 254.5Vac ± 2% |
Low Voltage Transfer |
85Vac ± 2% ; 170Vac ± 2% |
Low Voltage Return |
90Vac ± 2% ; 180Vac ± 2% |
High Voltage Transfer |
150Vac ± 2% ; 300Vac ± 2% |
High Voltage Return |
145Vac ± 2% ; 290Vac ± 2% |
OUTPUT |
Voltage |
110/115/120Vac or 220/230/240Vac re-settable via LCD panel |
Voltage
Regulation |
Line Mode |
± 15% |
Battery Mode |
< 3% RMS for entire battery voltage range |
Frequency
Regulation |
Line Mode |
Synchronize to AC main |
Battery Mode |
50Hz or 60Hz ± 0.1Hz |
Power Factor |
0.625 |
Wave Form |
Pure sine wave |
Efficiency |
> 80% |
Overload
Protection |
Line Mode |
> 110%, then buzzer alarm and amber LED blink continuously |
Battery Mode |
110%~150% : 30 sec, >150% : 200ms, then UPS shutdown |
Short Circuit
Protection |
Line Mode |
Circuit breaker |
Battery Mode |
Electronic circuit |
DC START |
Cold Start |
Yes |
TRANSFER TIME |
Typical |
< 4 ms |
BATTERY |
Voltage |
12Vdc |
24Vdc |
36Vdc |
36Vdc |
Type |
9AH |
7AH |
7AH |
9AH |
Quantity |
1pce |
2pcs |
3pcs |
3pcs |
Backup Time |
> 2min |
> 3 min |
Recharging Current |
0.1C |
0.1C ~ 0.3C |
CONTROL PANEL |
LCD Display |
UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage &level, Temperature, Model |
LED |
Normal(Green), Warning (Amber), Fault (Red) |
AUDIBLE ALARM |
Battery Mode |
Beeping every 4 seconds |
Low Battery |
Beeping every second |
UPS Fault |
Beeping continuously |
Overload |
Beeping twice per second |
COMMUNICATION INTERFACES |
Standard |
USB |
RS232 |
Multi-Interfaces Card(Option) |
N/A |
Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time |
ENVIRONMENT |
Operation Temperature |
0-40 ℃(32-104 ℉) |
Relative Humidity |
0-95% (non-condensing) |
Audible Noise(At 1M) |
< 55dBA |
PHYSICAL |
Dimensions(W*H*D)mm |
115*322*130 |
145*215*365 |
145*215*431 |
Net Weight (Kg) w/o battery |
3.2 |
8.6 |
10.4 |
12.2 |
NEMA Outlets
(110/115/120Vac) |
3 |
4 |
6 |
IEC Outlets
(220/230/240Vac) |
4 |
3 |
6 |
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice |
MODEL |
APA-103U |
APA-153U |
Capacity |
VA/Watt |
1kVA/625W |
1.5kVA/938W |
Mode Type |
Rack |
INPUT |
Nominal Voltage |
110/115/120 Vac or 220/230/240Vac |
Voltage Range |
Acceptable
Voltage Range |
85Vac ~ 150Vac or 170Vac ~ 300Vac |
Frequency |
45Hz ~ 70Hz Auto-sensing |
Boost Transfer |
97.8Vac ± 2% ; 195.5Vac ± 2% |
Boost Return |
102.8Vac ± 2% ; 205.5Vac ± 2% |
Buck Transfer |
132Vac ± 2% ; 264.5Vac ± 2% |
Buck Return |
127Vac ± 2% ; 254.5Vac ± 2% |
Low Voltage Transfer |
85Vac ± 2% ; 170Vac ± 2% |
Low Voltage Return |
90Vac ± 2% ; 180Vac ± 2% |
High Voltage Transfer |
150Vac ± 2% ; 300Vac ± 2% |
High Voltage Return |
145Vac ± 2% ;290Vac ± 2% |
OUTPUT |
Voltage |
110/115/120Vac or 220/230/240Vac re-settable via LCD panel |
Voltage
Regulation |
Line Mode |
± 15% |
Battery Mode |
< 3% RMS for entire battery voltage range |
Frequency Regulation |
Line Mode |
Synchronize to AC main |
Battery Mode |
50Hz or 60Hz ± 0.1Hz |
Power Factor |
0.625 |
Wave Form |
Pure sine wave |
Efficiency |
> 80% |
Overload
Protection |
Line Mode |
> 110%, then buzzer alarm and amber LED blink continuously |
Battery Mode |
110%~150% : 30 sec, >150% : 200ms, then UPS shutdown |
Short Circuit
Protection |
Line Mode |
Circuit breaker |
Battery Mode |
Electronic circuit |
DC START |
Cold Start |
Yes |
TRANSFER TIME |
Typical |
< 4 ms |
BATTERY |
Voltage |
24Vdc |
Type |
7AH |
Quantity |
4pcs |
Backup Time |
> 3 min |
Recharging Current |
0.1C ~ 0.3C |
CONTROL PANEL |
LCD Display |
UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model |
LED |
Normal (Green), Warning (Amber), Fault (Red) |
AUDIBLE ALARM |
Battery Mode |
Beeping every 4 seconds |
Low Battery |
Beeping every second |
UPS Fault |
Beeping continuously |
Overload |
Beeping twice per second |
COMMUNICATION INTERFACES |
Standard |
RS232 |
Multi-Interfaces Card(Option) |
Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time |
ENVIRONMENT |
Operation Temperature |
0-40 ℃(32-104 ℉) |
Relative Humidity |
0-95% (non-condensing) |
Audible Noise(At 1M) |
< 55dBA |
PHYSICAL |
Dimensions(W*H*D)mm |
440*44*515 |
Net Weight (Kg) w/o battery |
12 |
14.1 |
NEMA Outlets
(110/115/120Vac) |
4 |
IEC Outlets
(220/230/240Vac) |
5 |
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah
✽ Dimension:W*H*D=440*132*465mm. 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice |
MODEL |
APA-103TR |
APA-153TR |
APA-203TR |
APA-303TR |
APA-503TR |
APA-753TR |
APA-104TR |
Capacity |
VA/ Watt |
1kVA/
625W |
1.5kVA/
938W |
2kVA/
1250W |
3kVA/
1875W |
5kVA/
3125W |
7.5kVA/
4688W |
10kVA/
6250W |
Mode Type |
Tower & Rack convertible |
INPUT |
Nominal Voltage |
110/115/120 Vac or 220/230/240Vac |
220/230/240Vac |
Voltage Range |
Acceptable Voltage Range |
85Vac ~ 150Vac or 170Vac ~ 300Vac |
170Vac ~ 300Vac |
Frequency |
45Hz ~ 70Hz Auto-sensing |
Boost Transfer |
97.8Vac ± 2% ; 195.5Vac ± 2% |
195.5Vac ± 2% |
Boost Return |
102.8Vac ± 2% ; 205.5Vac ± 2% |
205.5Vac ± 2% |
Buck Transfer |
132Vac ± 2% ; 264.5Vac ± 2% |
264.5Vac ± 2% |
Buck Return |
127Vac ± 2% ; 254.5Vac ± 2% |
254.5Vac ± 2% |
Low Voltage Transfer |
85Vac ± 2% ; 170Vac ± 2% |
170Vac ± 2% |
Low Voltage Return |
90Vac ± 2% ; 180Vac ± 2% |
180Vac ± 2% |
High Voltage Transfer |
150Vac ± 2% ; 300Vac ± 2% |
300Vac ± 2% |
High Voltage Return |
145Vac ± 2% ; 290Vac ± 2% |
290Vac ± 2% |
OUTPUT |
Voltage |
110/115/120Vac or 220/230/240Vac re-settable via LCD panel |
Voltage
Regulation |
Line Mode |
± 15% |
Battery Mode |
< 3% RMS for entire battery voltage range |
Frequency
Regulation |
Line Mode |
Synchronize to AC main |
Battery Mode |
50Hz or 60Hz ± 0.1Hz |
Power Factor |
0.625 |
Wave Form |
Pure sine wave |
Efficiency |
> 80% |
Overload
Protection |
Line Mode |
> 110%, then buzzer alarm and amber LED blink continuously |
Battery Mode |
110%~150% : 30 sec, >150% : 200ms, then UPS shutdown |
Short Circuit
Protection |
Line Mode |
Circuit breaker |
Battery Mode |
Electronic circuit |
DC START |
Cold Start |
Yes |
TRANSFER TIME |
Typical |
< 4 ms |
Battery |
Voltage |
24Vdc |
36Vdc |
36Vdc |
36Vdc |
48Vdc |
48Vdc |
Type |
7AH |
7AH |
9AH |
7AH |
9AH |
7AH |
9AH |
Quantity |
2pcs |
3pcs |
3pcs |
6pcs |
8pcs |
16pcs |
16pcs |
Backup Time |
> 3 min |
Recharging Current |
0.1C ~ 0.3C |
CONTROL PANEL |
LCD Display |
UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model |
LED |
Normal(Green), Warning (Amber), Fault (Red) |
AUDIBLE ALARM |
Battery Mode |
Beeping every 4 seconds |
Low Battery |
Beeping every second |
UPS Fault |
Beeping continuously |
Overload |
Beeping twice per second |
COMMUNICATION INTERFACES |
Standard |
RS232 |
Multi-Interfaces Card(Option) |
Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time |
ENVIRONMENT |
Operation Temperature |
0-40 ℃(32-104 ℉) |
Relative Humidity |
0-95% (non-condensing) |
Audible Noise(At 1M) |
< 55dBA |
PHYSICAL |
Dimensions(W*H*D)mm |
440*88*465 |
440*132*465 |
440*132*620 |
440*132*465 |
Net Weight (Kg) w/o battery |
15.6 |
17.1 |
17.5 |
22.8 |
29.4 |
31.4 |
36.4 |
NEMA Outlets
(110/115/120Vac) |
4 |
8 |
8+1*
terminal block |
4+1*terminal block |
IEC Outlets
(220/230/240Vac) |
6 |
10 |
10+1*
terminal block |
5+1*terminal block |
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice |
MODEL |
APA-103TRL |
APA-153TRL |
APA-203TRL |
APA-303TRL |
APA-503TRL |
APA-753TRL |
Capacity |
VA/Watt |
1kVA/625W |
1.5kVA/938W |
2kVA/1250W |
3kVA/1875W |
5kVA/3125W |
7.5kVA/4688W |
Mode Type |
Tower & Rack convertible |
INPUT |
Nominal Voltage |
110/115/120 Vac or 220/230/240Vac |
220/230/240Vac |
Voltage Range |
Acceptable Voltage Range |
85Vac ~ 150Vac or 170Vac ~ 300Vac |
170Vac ~ 300Vac |
Frequency |
45Hz ~ 70Hz Auto-sensing |
Boost Transfer |
97.8Vac ± 2% ; 195.5Vac ± 2% |
195.5Vac ± 2% |
Boost Return |
102.8Vac ± 2% ; 205.5Vac ± 2% |
205.5Vac ± 2% |
Buck Transfer |
132Vac ± 2% ; 264.5Vac ± 2% |
264.5Vac ± 2% |
Buck Return |
127Vac ± 2% ; 254.5Vac ± 2% |
254.5Vac ± 2% |
Low Voltage Transfer |
85Vac ± 2% ; 170Vac ± 2% |
170Vac ± 2% |
Low Voltage Return |
90Vac ± 2% ; 180Vac ± 2% |
180Vac ± 2% |
High Voltage Transfer |
150Vac ± 2% ; 300Vac ± 2% |
300Vac ± 2% |
High Voltage Return |
145Vac ± 2% ;290Vac ± 2% |
290Vac ± 2% |
OUTPUT |
Voltage |
110/115/120Vac or 220/230/240Vac re-settable via LCD panel |
Voltage Regulation |
Line Mode |
± 15% |
Battery Mode |
< 3% RMS for entire battery voltage range |
Frequency Regulation |
Line Mode |
Synchronize to AC main |
Battery Mode |
50Hz or 60Hz ± 0.1Hz |
Power Factor |
0.625 |
Wave Form |
Pure sine wave |
Efficiency |
> 80% |
Overload Protection |
Line Mode |
> 110%, then buzzer alarm and amber LED blink continuously |
Battery Mode |
110%~150% : 30 sec, >150% : 200ms, then UPS shutdown |
Short Circuit Protection |
Line Mode |
Circuit breaker |
Battery Mode |
Electronic circuit |
DC START |
Cold Start |
Yes |
TRANSFER TIME |
Typical |
< 4 ms |
BATTERY |
Voltage |
24Vdc |
36Vdc |
36Vdc |
48Vdc |
Type |
N/A |
Quantity |
N/A |
Backup Time |
Based on Load % & Batteries |
CONTROL PANEL |
LCD Display |
UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model |
LED |
Normal (Green), Warning (Amber), Fault (Red) |
AUDIBLE ALARM |
Battery Mode |
Beeping every 4 seconds |
Low Battery |
Beeping every second |
UPS Fault |
Beeping continuously |
Overload |
Beeping twice per second |
COMMUNICATION INTERFACES |
Standard |
RS232 |
Multi-Interfaces Card(Option) |
Various Comb. of RS232, SNMP, USB, Dry Contact, AS400,
Enable at the same time |
ENVIRONMENT |
Operation Temperature |
0-40 ℃(32-104 ℉) |
Relative Humidity |
0-95% (non-condensing) |
Audible Noise(At 1M) |
< 55dBA |
PHYSICAL |
Dimensions(W*H*D)mm |
440*88*465 |
440*132*465 |
Net Weight (Kg) |
14 |
16.4 |
21 |
25.5 |
31.4 |
36.4 |
NEMA Outlets
(110/115/120Vac) |
6 |
10 |
8 |
4+1*terminal block |
4+1*terminal block |
IEC Outlets
(220/230/240Vac) |
6 |
10 |
10 |
5+1*terminal block |
5+1*terminal block |
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice |
MODEL |
APA-103TL |
APA-153TL |
Capacity |
VA / Watt |
1kVA/625W |
1.5kVA/938W |
Mode Type |
Tower |
INPUT |
Nominal Voltage |
110/115/120 Vac or 220/230/240Vac |
Voltage Range |
Acceptable
Voltage Range |
85Vac ~ 150Vac or 170Vac ~ 300Vac |
Frequency |
45Hz ~ 70Hz Auto-sensing |
Boost Transfer |
97.8Vac ± 2% ; 195.5Vac ±2% |
Boost Return |
102.8Vac ± 2% ; 205.5Vac ± 2% |
Buck Transfer |
132Vac ± 2% ; 264.5Vac ± 2% |
Buck Return |
127Vac ± 2% ; 254.5Vac ± 2% |
Low Voltage Transfer |
85Vac ± 2% ; 170Vac ± 2% |
Low Voltage Return |
90Vac ± 2% ; 180Vac ± 2% |
High Voltage Transfer |
150Vac ± 2% ; 300Vac ± 2% |
High Voltage Return |
145Vac ± 2% ; 290Vac ± 2% |
OUTPUT |
Voltage |
110/115/120Vac or 220/230/240Vac re-settable via LCD panel |
Voltage
Regulation |
Line Mode |
± 15% |
Battery Mode |
< 3% RMS for entire battery voltage range |
Frequency Regulation |
Line Mode |
Synchronize to AC main |
Battery Mode |
50Hz or 60Hz ± 0.1Hz |
Power Factor |
0.625 |
Wave Form |
Pure sine wave |
Efficiency |
Line Mode |
> 98% |
Battery Mode |
> 80% |
Overload
Protection |
Line Mode |
> 110%, then buzzer alarm and amber LED blink continuously |
Battery Mode |
110%~150% : 30 sec, >150% : 200ms, then UPS shutdown |
Short Circuit
Protection |
Line Mode |
Circuit breaker |
Battery Mode |
Electronic circuit |
DC START |
Cold Start |
Yes |
TRANSFER TIME |
Typical |
< 4 ms |
BATTERY |
Voltage |
24Vdc |
36Vdc |
Type |
N/A |
Quantity |
N/A |
Backup Time |
> 3 min |
CONTROL PANEL |
LCD Display |
UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model |
LED |
Normal (Green), Warning (Amber), Fault (Red) |
AUDIBLE ALARM |
Battery Mode |
Beeping every 4 seconds |
Low Battery |
Beeping every second |
UPS Fault |
Beeping continuously |
Overload |
Beeping twice per second |
COMMUNICATION INTERFACES |
Standard |
RS232 |
Multi-Interfaces Card(Option) |
Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time |
ENVIRONMENT |
Operation Temperature |
0-40 ℃(32-104 ℉) |
Relative Humidity |
0-95% (non-condensing) |
Audible Noise(At 1M) |
< 55dBA |
PHYSICAL |
Dimensions(W*H*D)mm |
145*215*365 |
145*215*431 |
Net Weight (Kg) |
11.6 |
12.6 |
NEMA Outlets
(110/115/120Vac) |
3 |
6 |
IEC Outlets
(220/230/240Vac) |
3 |
6 |
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank ✽All specifications mentioned above are subject to change without prior notice |
|