Products > UPS > APA Series ( 650VA-10kVA )



UPS
 

Features

Pure sine wave for both linear & non-linear loads
Complete range from 650VA to 10kVA
Various models for Tower, Rack 1U/2U/3U, Tower & Rack convertible
Standard and long backup time models available
Optional multiple interface cards (RS232, multiple card, SNMP card, dry contact card, AS400 card and USB card)
Complete protections for overload, overheat, surges, spikes, short circuit and over charge and fool-proof wiring installation
User –friendly easy swap battery replacement design
Built-in powerful charger with input power factor correction
Optional Emergency Power Off (EPO) available for rack model
Intelligent fan speed control
DC start
MODEL APA-650 LED APA-103T APA-153T APA-203T
Capacity VA / Watt 650VA/406W 1kVA/625W 1.5kVA/938W 2kVA/1250W
Mode Type Tower
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%  
Buck Return 127Vac ± 2% ; 254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return  145Vac ± 2% ;  290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 12Vdc 24Vdc 36Vdc 36Vdc
Type 9AH 7AH 7AH 9AH
Quantity 1pce 2pcs 3pcs 3pcs
Backup Time > 2min > 3 min
Recharging Current 0.1C 0.1C ~ 0.3C
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage &level, Temperature, Model
LED Normal(Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery  Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard USB  RS232
Multi-Interfaces Card(Option) N/A Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 115*322*130 145*215*365 145*215*431
Net Weight (Kg) w/o battery 3.2 8.6 10.4 12.2
NEMA Outlets
(110/115/120Vac)
3 4 6
IEC  Outlets
(220/230/240Vac)
4 3 6
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
 ✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103U APA-153U
Capacity VA/Watt 1kVA/625W 1.5kVA/938W
Mode Type Rack
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac 
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode  > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc
Type 7AH
Quantity 4pcs
Backup Time > 3 min
Recharging Current 0.1C ~ 0.3C
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model
LED Normal (Green), Warning (Amber), Fault (Red) 
AUDIBLE ALARM
Battery  Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*44*515
Net Weight (Kg) w/o battery 12 14.1
NEMA Outlets
(110/115/120Vac)
4
IEC Outlets
(220/230/240Vac)
5
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah
✽ Dimension:W*H*D=440*132*465mm. 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TR APA-153TR APA-203TR APA-303TR APA-503TR APA-753TR APA-104TR
Capacity VA/ Watt 1kVA/
625W
1.5kVA/
938W
2kVA/
1250W 
3kVA/
1875W
5kVA/
3125W 
7.5kVA/
4688W 
10kVA/
6250W 
Mode Type   Tower & Rack convertible
INPUT
 Nominal Voltage  110/115/120 Vac or 220/230/240Vac   220/230/240Vac 
 Voltage Range Acceptable Voltage Range 85Vac ~ 150Vac or 170Vac ~ 300Vac 170Vac ~ 300Vac
 Frequency  45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2%  195.5Vac ± 2% 
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2%  205.5Vac ± 2% 
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2% 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%  254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2% 170Vac ± 2%
Low Voltage Return  90Vac ± 2% ; 180Vac ± 2% 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2% 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;  290Vac ± 2% 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode Synchronize to AC main
Battery Mode  50Hz or 60Hz ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload
Protection
Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown 
Short Circuit
Protection
Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
Battery
Voltage 24Vdc 36Vdc 36Vdc 36Vdc 48Vdc 48Vdc
Type 7AH 7AH 9AH 7AH 9AH 7AH 9AH
Quantity 2pcs 3pcs 3pcs 6pcs 8pcs 16pcs 16pcs
Backup Time > 3 min
Recharging Current 0.1C ~ 0.3C
CONTROL PANEL 
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model  
LED Normal(Green), Warning (Amber), Fault (Red) 
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds 
Low Battery Beeping every second 
UPS Fault Beeping continuously 
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard  RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*88*465 440*132*465 440*132*620 440*132*465
Net Weight (Kg) w/o battery  15.6 17.1 17.5 22.8 29.4  31.4 36.4
NEMA Outlets
(110/115/120Vac) 
 4 8 8+1*
terminal block
4+1*terminal block  
IEC Outlets
(220/230/240Vac)
6 10 10+1*
terminal block
5+1*terminal block
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TRL APA-153TRL APA-203TRL APA-303TRL APA-503TRL APA-753TRL
Capacity VA/Watt 1kVA/625W 1.5kVA/938W 2kVA/1250W 3kVA/1875W 5kVA/3125W 7.5kVA/4688W
Mode Type Tower & Rack convertible
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac  220/230/240Vac
Voltage Range Acceptable Voltage Range 85Vac ~ 150Vac or 170Vac ~ 300Vac 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ± 2% 195.5Vac ± 2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2% 205.5Vac ± 2%
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2% 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2%  254.5Vac ± 2%
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%  170Vac ± 2%
Low Voltage Return  90Vac ± 2% ; 180Vac ± 2% 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2% 300Vac ± 2%
High Voltage Return 145Vac ± 2% ;290Vac ± 2% 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage Regulation Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency Regulation Line Mode Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency > 80%
Overload Protection Line Mode > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit Protection Line Mode Circuit breaker
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc  36Vdc 36Vdc 48Vdc
Type N/A
Quantity N/A
Backup Time Based on Load % & Batteries
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model
LED Normal (Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 440*88*465 440*132*465
Net Weight (Kg) 14 16.4 21 25.5 31.4 36.4
NEMA Outlets
(110/115/120Vac)
6 10 8 4+1*terminal block 4+1*terminal block
IEC Outlets
(220/230/240Vac)
6 10 10 5+1*terminal block 5+1*terminal block
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽ All specifications mentioned above are subject to change without prior notice
MODEL APA-103TL APA-153TL
Capacity VA / Watt 1kVA/625W 1.5kVA/938W
Mode Type  Tower
INPUT
Nominal Voltage 110/115/120 Vac or 220/230/240Vac
Voltage Range Acceptable
Voltage Range
85Vac ~ 150Vac or 170Vac ~ 300Vac
Frequency 45Hz ~ 70Hz Auto-sensing
Boost Transfer 97.8Vac ± 2% ; 195.5Vac ±2%
Boost Return 102.8Vac ± 2% ; 205.5Vac ± 2%
Buck Transfer 132Vac ± 2% ; 264.5Vac ± 2%
Buck Return 127Vac ± 2% ; 254.5Vac ± 2% 
Low Voltage Transfer 85Vac ± 2% ; 170Vac ± 2%
Low Voltage Return 90Vac ± 2% ; 180Vac ± 2%
High Voltage Transfer 150Vac ± 2% ; 300Vac ± 2%
High Voltage Return 145Vac ± 2% ; 290Vac ± 2%
OUTPUT
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage
Regulation
Line Mode ± 15%
Battery Mode < 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode  Synchronize to AC main
Battery Mode 50Hz or 60Hz  ± 0.1Hz
Power Factor 0.625
Wave Form Pure sine wave
Efficiency Line Mode  > 98%
Battery Mode > 80%
Overload
Protection
Line Mode  > 110%, then buzzer alarm and amber LED blink continuously
Battery Mode 110%~150% : 30 sec, >150% : 200ms, then UPS shutdown
Short Circuit
Protection
Line Mode Circuit breaker 
Battery Mode Electronic circuit
DC START
Cold Start Yes
TRANSFER TIME
Typical < 4 ms
BATTERY
Voltage 24Vdc 36Vdc
Type N/A
Quantity N/A
Backup Time > 3 min
CONTROL PANEL
LCD Display UPS status, I/P&O/P Voltage/Frequency, Load level, Battery voltage & level, Temperature, Model 
LED Normal (Green), Warning (Amber), Fault (Red)
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
UPS Fault Beeping continuously
Overload Beeping twice per second
COMMUNICATION INTERFACES
Standard RS232
Multi-Interfaces Card(Option) Various Comb. of RS232, SNMP, USB, Dry Contact, AS400, Enable at the same time
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 145*215*365 145*215*431
Net Weight (Kg) 11.6 12.6
NEMA Outlets
(110/115/120Vac)
3 6
IEC Outlets
(220/230/240Vac)
3 6
✽ Rack Battery Bank APA BTR16:for 16 pcs 12V/7Ah or 16pcs 12V/9Ah.Dimension:W*H*D=440*132*465mm
✽ 7.5-10kVA connect to an external battery bank
✽All specifications mentioned above are subject to change without prior notice