Products > New Products >AHA-N700/N700L/N1K/N1KL



UPS

UPS
 

Features

Advanced microprocessor design base
True sine wave output
Input power factor correction 0.99
Perfect failure protection
Generator compatible
Wide input range, high efficiency
50Hz/60Hz auto-detect
USB HID communication built-in

MODEL AHA-N700 AHA-N700L AHA-N1K AHA-N1KL
Capacity VA / Watt 700VA/420W 700VA/320W 1000VA/900W 1000VA/800W
INPUT
Voltage Range Acceptable Voltage Range 55Vac-150Vac or 110Vac-300Vac
Low Line Transfer 85Vac / 55Vac or 170Vac / 110Vac( Based on load percentage 100% - 60% / 60% - 0%)
Line Low Return 90Vac / 110Vac or 180Vac / 120Vac ± 5 %
Line High Transfer 150Vac or 300Vac ± 5 %
Line High Return 145Vac or 290Vac ± 5 %
Frequency Range 50Hz / 60Hz  Auto sensing ( 47Hz - 53Hz / 57Hz - 63Hz) 
Phase Single phase with ground
Power Factor
(I/P:220V Battery full charged, output @ full load)
> 0.99 @ Nominal voltage (100 % load)
OUTPUT
Waveform Pure sine wave
Voltage 110Vac/115Vac/120Vac or 220Vac/230Vac/240Vac
Voltage Regulation Line Mode ± 1 %
Battery Mode ± 1 %
Frequency Regulation Line Mode Synchronize to AC main
Battery Mode 50Hz / 60Hz ± 0.1 Hz
Current Crest Ratio 4 : 1
Harmonic Distortion ≦ 4% (Linear load), ≦ 6%(Non-linear load)
Transfer Time AC Mode to Batt. Mode Zero
Inverter Mode to Bypass 4 ms (Typical)
Efficiency AC Mode
(Battery full charged)
> 89.5 %
Battery Mode > 86.5% > 88.5%
Overload Protection Line Mode 110% - 120% : 10s , > 120% : 200ms 
(and go to bypass. If the overload condition is remover, the unit will return back to inverter automatically)
Battery Mode 110% - 120%: 10s , > 120% : 200ms then UPS shutdown
 DC START
Cold Start  Yes
BATTERY
Voltage 12Vdc 24Vdc
Type  12V / 7Ah  Depending on the capacity of external batteries 12V / 7Ah  Depending on the capacity of external batteries
Quantity 1 2
Recharging Current(max.) 1.0A 4A or 9A 1.0A 4A or 8A
Charging Voltage 13.6Vdc ± 1% 27.3Vdc ± 1%
DISPLAY
LCD (Option) N / A UPS status, I/P&O/P voltage/frequency, load level, battery voltage
LED  Green: Normal (Continuously), Warning (Flash) Normal (Green), Warning (Amber), Fault (Red) 
AUDIBLE ALARM
Battery  Mode Beeping every 4 seconds 
Low Battery Beeping every second
UPS Fault Beeping continuously 
Overload Beeping twice per second
COMMUNICATION PORT
Standard Configuration  HID (Human Interface Device)
ENVIRONMENT
Operation Temperature 0-40 ℃(32-104 ℉)
Relative Humidity 0-95% (non-condensing)
Audible Noise(At 1M) < 55dBA
PHYSICAL
Dimensions(W*H*D)mm 115 *163 * 271 145 * 300 * 325
Net Weight(Kg)  5.0 2.9 8.8 4.3
✽ All specifications mentioned above are subject to change without prior notice
Download Brochure
AHA-N Series