| MODEL |
AHA- 103H/HR |
AHA- 203H/HR |
AHA- 303H/HR |
| Capacity |
VA / Watt |
1kVA/700W |
2kVA/1400W |
3kVA/2100W |
| INPUT |
| Phase |
Single Phase |
| Nominal Voltage |
110Vac/220Vac |
| Voltage Range |
160-300Vac(70%-100%load),140-300Vac
(50%-70% load),110-300Vac (0%-50% load) |
| Frequency |
50Hz / 60Hz ± 4Hz |
| Power Factor |
≥0.95 |
≥0.97 |
OUTPUT |
| Voltage |
220VAC ± 2% (230V or 240V re-settable via LCD panel)
110VAC ± 2%(110V,115V or 120V re-settable via LCD panel)
|
| Frequency |
Synchronized ( Line mode); 50Hz or 60Hz +/-0.5% (Battery mode) |
| Wave Form |
True sine wave |
| Distortion |
Tower |
≤3% (Linear load)
≤6% (Non-linear load) |
≤4% (Linear load)
≤7% (Non-linear load) |
| Rack |
≤4% (Linear load) ,≤7% (Non-linear load) |
| Overload Capacity |
112%~150% : 30sec. ; >150%: 200msec. |
| Crest Ratio |
3:1 |
BATTERY |
| DC Voltage |
36V |
96V |
| Capacity |
12V / 7Ah×3 pcs |
12V / 7Ah×8pcs |
| Back-up Time |
>5min |
>9min |
> 5min |
CHARGER |
| Built-In /Option |
1 Amp(standard) ; 8 Amp(long backup) |
1 Amp(standard) ; 9 Amp(long backup) |
| Recharging Time |
5 hrs to 90% |
BYPASS |
| Automatic |
Overload or UPS fault |
| By Setting |
Voltage range: 176~256V±20V (Re-settable via LCD panel) |
| Transfer Time |
0 ms( 2.5ms inverter to bypass) |
INDICATOR |
| LCD (Series) |
UPS status, I/P&O/P voltage/frequency, load %, battery voltage, battery capacity %, temperature, model spec., event log.
LED: Normal (Green), Warning (Yellow), Fault (Red)
|
| LED (Series) |
Normal (Green), Bypass(Yellow), Battery low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault (Red) |
OUTLET |
| Tower |
NEMAx3pcs
or IEC320x4pcs |
NEMA*3pcs+TB*1 or NEMA*6pcs
or IEC320x6pcs |
NEMA*3pcs+TB*1 or NEMA*6pcs
or IEC320x3+ TBx1 |
| Rack |
NEMAx4pcs
or IEC320x4pcs |
NEMAx2+TBx1
or IEC320x4pcs |
NEMAx2+TBx1
or IEC320x1+TBx1 |
AUDIBLE ALARM |
| Battery Mode |
Beeping every 4 seconds (re-settable) |
| Battery Low |
Beeping every second |
| Overload |
Beeping twice per second |
| Fault |
Beeping continuously |
INTERFACE |
| RS-232 Interface |
UPSilon2000 monitoring software for Windows all, Unix systems and Novell |
| Multi-Interface Slot |
SNMP card, AS 400, dry contact, USB selectable |
Network |
| Surge Protection |
RJ45 I/O port for Network or RJ 11 for Fax / Modem |
|
| Parallel |
N/A |
ENVIRONMENT |
| Temperature |
0-40 ℃(32-104 ℉) |
| Humidity |
0-95% (non-condensing) |
| Audible Noise(At 1M ) |
<45 dBA |
<50 dBA |
PHYSICAL |
| Weight(Kg, without battery) |
6.5(Tower)
8.0(Rack) |
13.5(Tower)
9.5(Rack) |
14.5(Tower)
10.5(Rack) |
| Weight(Kg, with battery) |
15(Tower)
15.5(Rack) |
34(Tower)
N/A (Rack) |
35(Tower)
N/A(Rack) |
Dimensions
(W*H*D)mm |
Tower |
160*220*400 |
200*352*450 |
| Rack |
440*88*465 |
| Color |
White or black |
✽ Tower Series: AHA-H,Rack Series: AHA-HR ✽ Output power factor 0.8 is available
✽ Rack Battery Bank(2U) is available for 8pcs( 1 set)12V/7Ah and 9 pcs( 3 sets)12V/7Ah batteries
✽ 1kVA/3kVA 110V is available
✽ All specifications mentined above are sujbect to change without prior notice |