Products > UPS > AHA-H Series ( High Frequency Type:1kVA-3kVA )

UPS
 

Features

Multiple microprocessor high frequency design and DSP technology
Unity input power factor and wide input range
Pure sine-wave double conversion on-line UPS
DC start and automatic self-diagnostic function
RS232 communication port and intelligent slot selectable:
Smart RS232(standard) ; Optional: SNMP card, AS-400card, USB card and dry contact card
High efficiency design to save electricity
Low heat dissipation in long term operation
Designed to operate under harsh environment
MODEL AHA-
103H/HR
AHA-
203H/HR
AHA-
303H/HR
Capacity VA / Watt 1kVA/700W 2kVA/1400W 3kVA/2100W
INPUT
Phase Single Phase
Nominal Voltage 110Vac/220Vac
Voltage Range 160-300Vac(70%-100%load),140-300Vac
(50%-70% load),110-300Vac (0%-50% load)
Frequency 50Hz / 60Hz ± 4Hz
Power Factor ≥0.95 ≥0.97
OUTPUT
Voltage 220VAC ± 2% (230V or 240V re-settable via LCD panel)
110VAC ± 2%(110V,115V or 120V re-settable via LCD panel)
Frequency Synchronized ( Line mode); 50Hz or 60Hz +/-0.5% (Battery mode)
Wave Form True sine wave
Distortion Tower ≤3% (Linear load)
≤6% (Non-linear load)
≤4% (Linear load)
≤7% (Non-linear load)
Rack ≤4% (Linear load) ,≤7% (Non-linear load)
Overload Capacity 112%~150% : 30sec. ; >150%: 200msec.
Crest Ratio 3:1
BATTERY
DC Voltage 36V 96V
Capacity 12V / 7Ah×3 pcs 12V / 7Ah×8pcs
Back-up Time >5min >9min > 5min
CHARGER
Built-In /Option 1 Amp(standard) ; 8 Amp(long backup) 1 Amp(standard) ; 9 Amp(long backup)
Recharging Time 5 hrs to 90%
BYPASS
Automatic Overload or UPS fault
By Setting Voltage range: 176~256V±20V (Re-settable via LCD panel)
Transfer Time 0 ms( 2.5ms inverter to bypass)
INDICATOR
LCD (Series) UPS status, I/P&O/P voltage/frequency, load %, battery voltage, battery capacity %, temperature, model spec., event log.
LED: Normal (Green), Warning (Yellow), Fault (Red)
LED (Series) Normal (Green), Bypass(Yellow), Battery low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault (Red)
OUTLET
Tower NEMAx3pcs
or IEC320x4pcs
NEMA*3pcs+TB*1 or NEMA*6pcs
or IEC320x6pcs
NEMA*3pcs+TB*1 or NEMA*6pcs
or IEC320x3+ TBx1 
Rack NEMAx4pcs
or IEC320x4pcs
NEMAx2+TBx1
or IEC320x4pcs
NEMAx2+TBx1
or IEC320x1+TBx1
AUDIBLE ALARM
Battery Mode Beeping every 4 seconds (re-settable)
Battery Low Beeping every second
Overload Beeping twice per second
Fault Beeping continuously
INTERFACE
RS-232 Interface UPSilon2000 monitoring software for Windows all, Unix systems and Novell
Multi-Interface Slot SNMP card, AS 400, dry contact, USB selectable
Network
Surge Protection RJ45 I/O port for Network or RJ 11 for Fax / Modem
 
Parallel N/A
ENVIRONMENT
Temperature 0-40 ℃(32-104 ℉)
Humidity 0-95% (non-condensing)
Audible Noise(At 1M ) <45 dBA <50 dBA
PHYSICAL
Weight(Kg, without battery)  6.5(Tower)
8.0(Rack) 
13.5(Tower)
9.5(Rack) 
 14.5(Tower)
10.5(Rack) 
Weight(Kg, with battery) 15(Tower)
15.5(Rack)
34(Tower)
N/A (Rack) 
35(Tower)
N/A(Rack) 
Dimensions
(W*H*D)mm
Tower 160*220*400 200*352*450
Rack 440*88*465
Color White or black
✽ Tower Series: AHA-H,Rack Series: AHA-HR
✽ Output power factor 0.8 is available
✽ Rack Battery Bank(2U) is available for 8pcs( 1 set)12V/7Ah and 9 pcs( 3 sets)12V/7Ah batteries
✽ 1kVA/3kVA 110V is available
✽ All specifications mentined above are sujbect to change without prior notice
Download Brochure
AHA-H Series